single-dr.php

JDR Vol.5 No.6 pp. 712-719
(2010)
doi: 10.20965/jdr.2010.p0712

Paper:

Accidental Drop Load Effects on Buried Structures

Mehdi S. Zarghamee and Keng-Wit Lim

Simpson Gumpertz & Heger Inc. Engineering Mechanics and Infrastructure Division, 41 Seyon St., Building 1, Suite 500, Waltham, MA 02453, USA

Received:
April 29, 2010
Accepted:
October 13, 2010
Published:
December 1, 2010
Keywords:
steam generator replacement, drop load analysis, impact, stress wave propagation, structural evaluation, soil-structure interaction, soil damping, finite element analysis
Abstract
The finite-element model we propose to analyze the dynamics of accidental drop loads on critical buried structures during steam generator replacement includes representation of drop objects, impacted structures, soil media through which stress waves travel, and buried structures. Analysis accounts for the nonlinear effects of large deformation, steel plasticity and buckling, concrete cracking and crushing , and stress wave damping through soil. Stress and strain in buried structures is used to evaluate the condition of buried structures such as buried prestressed concrete and ductile iron pipelines and reinforced concrete structures housing critical components subjected to accidental drop loads during steam generator replacement near nuclear reactors operations.
Cite this article as:
M. Zarghamee and K. Lim, “Accidental Drop Load Effects on Buried Structures,” J. Disaster Res., Vol.5 No.6, pp. 712-719, 2010.
Data files:
References
  1. [1] Abaqus Version 6.9, Simulia, Dassault Systèmes.
  2. [2] American Concrete Institute, “Building Code Requirements for Structural Concrete,” ACI 318, 2005.
  3. [3] American Concrete Institute, “Code Requirements for Nuclear Safety-Related Concrete Structures and Commentary,” ACI 349, 2006.
  4. [4] American Water Works Association, “Standard for Thickness Design of Ductile-Iron Pipe,” AWWA C150, 2002.
  5. [5] American Water Works Association, “Standard for Design of Prestressed Concrete Cylinder Pipe,” AWWA C304, 2007.
  6. [6] American Water Works Association, “Concrete Pressure Pipe,” AWWA Manual M9, 2008.
  7. [7] UDP Program, developed by Simpson Gumpertz & Heger Inc. for the American Concrete Pressure Pipe Association, 2007.
  8. [8] M. S. Zarghamee and K-L Fok, “Analysis of Prestressed Concrete Pipe Under Combined Loads,” Journal of Structural Engineering. Vol.116, No.7, pp. 2022-2039, 1990.
  9. [9] M. S. Zarghamee, K.-W. Lim, and K. Henshaw, “Structural Evaluation of Drop Load Effects on Buried Structures,” 20th International Conference on Structural Mechanics in Reactor Technology (SMiRT 20), Espoo, Finland, August 2009.

*This site is desgined based on HTML5 and CSS3 for modern browsers, e.g. Chrome, Firefox, Safari, Edge, Opera.

Last updated on Apr. 22, 2024